Power System Analysis #40 | Stability I: The Swing Equation and Machine Model

Power System Stability

Instructor: Dr. Süleyman Burak ÇELİK

When a transmission line opens, the generator's electrical output drops. For an instant the turbine still delivers the same power, so the rotor accelerates and starts to run ahead of the grid. In this lesson we calculate that acceleration, the equilibrium angle and the restoring tendency with three original exam-style problems. In this lesson: - Accelerating power, the inertia constant and the swing equation - 500 MJ of rotor energy on a 100 MVA base and an electrical acceleration of 9.42 rad/s² - Converting the same machine's inertia from a 200 MVA base to a 100 MVA base - Constant internal voltage, total reactance and the infinite bus - The power–angle curve, the 30° operating point and synchronizing power - A small-signal natural frequency of about 1.44 Hz and a period of 0.69 s Chapters: 0:00 Why does the rotor speed up when a line opens? 0:46 Synchronous speed and power system stability 2:26 The electrical rotor angle 3:23 The inertia constant 4:18 The swing equation 5:26 Example 1 · Energy, power mismatch and acceleration 8:35 Example 2 · Changing the inertia base 9:42 The classical machine model and the infinite bus 10:47 Example 3 · The power–angle curve and equilibrium 12:07 The synchronizing power coefficient 13:21 Natural frequency and period 15:03 Summary and the equal-area question Reference textbook: J. Duncan Glover, Thomas J. Overbye, Adam B. Birchfield and Mulukutla S. Sarma, Power System Analysis and Design, SI Edition, 7th ed., Cengage, 2023, §12.1–12.2. The examples and drawings are original. Next lesson: the equal-area criterion. We will use the rotor's motion on the power–angle curve to find how quickly the circuit breaker must clear the fault.